SPECIFICATIONS |
|
|
|
|
650VA-3KVA |
|
|
|
Rated capacity |
|
1KVA |
1.5KVA |
2KVA |
3KVA |
|
|
|
input |
|
|
|
|
|
|
|
|
rated input voltage |
|
220V or 120V |
|
|
|
rated input range (the type of 220V) |
|
50Hz/60Hz auto-adaptive |
|
|
|
input voltage range (the type of 120V) |
|
(115-295)=5VAC (half load) (145-295)=5VAC (full load) |
|
|
|
input frequency range |
|
(55-145)=5VAC(60%load);(65-145)=5VAC(70% load)/ (75-145)=5VAC(80%load);(85-145)=5VAC(100%load) |
|
|
|
input current |
220V |
45-55Hz+/-0.5% 50Hz type |
|
|
|
120V |
55-65Hz+/-0.5% 60Hz type |
|
|
|
PFC |
|
≥0.98 |
|
|
|
THDI |
|
< 60% |
|
|
|
bypass voltage range |
220V |
rated output voltage -34v-rated output voltage + 32v |
|
|
|
120V |
(95-135)=5VAC |
|
|
|
output |
|
|
|
|
|
|
|
|
output voltage |
220V |
208VAC/210VAC/220VAC/240VAC setting available |
|
|
|
120V |
100/110/115/120/127VAC setting available |
|
|
|
Output PF |
|
0.8/0.9 |
0.8/0.9 |
0.8/0.9 |
0.8/0.9 |
|
|
|
output power (watt) |
|
800/900 |
1200/1350 |
1600/1800 |
2400/2700 |
|
|
|
inverter overload capacity |
|
105%-150% transfer to bypass mode after 30s giving alarm ; >150% transfer to bypass mode after 300ms giving alarm |
|
|
|
voltage accuracy |
|
1% |
|
|
|
load crest |
|
3:01 |
|
|
|
from AC mode to BAT mode |
|
0ms (transfer time) |
|
|
|
from BAT mode to AC mode |
|
0ms (transfer time) |
|
|
|
efficiency |
mains mode |
≥90% (full load) |
|
|
|
BAT mobe |
87% |
|
|
|
ECO mode |
94% |
|
|
|
output friquency |
|
|
|
|
|
|
|
|
under mains mode |
|
same as input frequency |
|
|
|
under battery mode |
|
(50/60=0.2)Hz |
|
|
|
phase-locked rate |
|
≤1Hz/s |
|
|
|
total voltage harmonic distortion |
|
full linear load<30%; full nonlinear load <5% |
|
|
|
battery |
|
|
|
|
|
|
|
|
battery type |
|
sealed lead acid maintenance free battery |
|
|
|
quantity |
|
2 |
3 |
4 |
4 |
6 |
6 |
8 |
dc voltage |
|
24V |
36V |
48V |
48V |
72V |
72V |
96V |
inbuilt battery |
|
9AH/12V |
7AH/12V |
9AH/12V |
9AH/12V |
7AH/12V |
9AH/12V |
7AH/12V |
output voltage |
|
27.1=0.4V |
40.6=0.5V |
54.2=0.6V |
54.2=0.6V |
81.3=0.9V |
81.3=0.9V |
108.4=1V |
backup time |
|
Based on battery capacity |
|
|
|
charge method |
|
three stage charging |
|
|
|
charge current |
|
standard model: 1A |
|
|
|
|
long time model: 6A |
|
|
|
system control and communication |
|
|
|
|
function |
silence, cold start,AC restart, Auto restart |
|
|
|
protection |
|
over-temp protection;fan testing protection;AC & N reversely connecting protection, output short circuit protection |
|
|
|
communication port software function |
Rs232; SNMP card; USB |
display |
|
LCD/LED |
|
|
|
|
|
|